4. Installation Specifications
4-14
TI 33Q01J10-01E Feb. 1, 2009-00
LOPXLMK
Table Periodic Replacement Parts Having Defined Life Spans (When average LOPXLMK ambient
temperature is 30 °C)
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Air filter T9050NY 1 year Yes Wash every 3 months.
Power supply unit S9961UK 8 years No
The electrolytic capacitor is a
part with a defined life span.
LCD unit S9388FA 3 years No –
LCD unit S9389FA 3 years No –
Fan unit AIP601 4 years Yes –
Operation keyboard S9390FA – No Depends on frequency of use.
Fuse
S9518VK 3 years Yes
For 100 V AC
(for service outlet)
A1353EF 3 years Yes
For 220 V AC
(for service outlet)
Relay S9725VM
100000
operations
Yes –
AIP826/AIP827
Table Periodic Replacement Parts Having Defined Life Spans (When average AIP826/AIP827 ambient
temperature is 30 °C)
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
AC adapter A1519UP 5 years Yes –