4. Installation Specifications
4-13
TI 33Q01J10-01E
YPCKIT
Table Periodic Replacement Parts Having Defined Life Spans (When average YPCKIT ambient
temperature is 30 °C)
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
LCD unit
S9205FA 3 years Yes 100 V AC
S9206FA 3 years Yes 200 V AC
Operation keyboard S9282FA
– No Depends on frequency of use.
AC adapter
(For operation keyboard)
A1519UP 5 years No
–
Fuse
S9518VK 3 years Yes
For 100 V AC
(for service outlet)
A1353EF 3 years Yes
For 220 V AC
(for service outlet)
Relay S9725VM
100000
operations
Yes –
LOPSVMK
Table Periodic Replacement Parts Having Defined Life Spans (When average LOPSVMK ambient
temperature is 30 °C)
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Air filter T9003BY 1 year Yes Wash every 3 months.
Power supply unit S9961UK 8 years No
The electrolytic capacitor is a
part with a defined life span.
LCD unit S9225FA 4 years No
–
Fan unit(*1)
A1025EM 4 years Yes 100 V AC
S9000VK 4 years Yes 110/115 V AC
A1043EM 4 years Yes 120 V AC
Operation keyboard
S9284FA
or
S9363FA
– No Depends on frequency of use.
Fuse S9518VK 3 years Yes for fan
Relay S9725VM
100000
operations
Yes –
*1: Users can replace a fan unit by themselves, but they are also required to do soldering.
YOKOGAWA service department can take on the work.
Feb. 1, 2009-00