1. System Installation Requirements
1-13
TI 33Q01J10-01E
JEIDA-63 classifications are shown below:
Table Classification of JEIDA-63 Environment Specifications
Class A Class B Class S (S1) Class S2 Class S3 (S4)
Temperature
and
humidity
Temperature 15 to 30 °C 5 to 40 °C 0 to 50 °C –10 to 60 °C –25 to 70 °C
Humidity 40 to 70 %RH 20 to 80 %RH 10 to 90 %RH 5 to 95 %RH
5 to 100 %RH
including
condensation
Temperature
fluctuation
±5 °C/h ±10 °C/h ±15 °C/h
Power
source
Voltage ±5 % ±10 % +15 %, –20 %
Frequency ±0.5 Hz ±1 Hz ±3 Hz
Distortion
factor
5 % or less 10 % or less 20 % or less
Peak value
reduction
2 % or less 5 % or less 10 % or less
Instantaneous
power failure
3 ms or less
10ms or less or
1/2 cycle or less
200 ms or less
Grounding
Dedicated class
A or C
Dedicated class D
Class D common
(excl. power
supply equipment)
Noise
Static
electricity (*1)
2 kV 4 kV 6 kV 8 kV Open
Electrical field 1 V/m or less 3 V/m or less 10 V/m or less (Special)
Continuous
wave
transmission
noise
1 V 3 V 10 V (Special)
Magnetic field 1 A/m or less 3 A/m or less 10 A/m or less 30 A/m or less
100 A/m or less
(Special)
Lightening
surge
0.5 kV 1.0 kV 2.0 kV 4.0 kV Special
Fast transient/
burst wave
noise
0.5 kV
(Repetitive ratio
5 kHz)
1.0 kV
(Repetitive ratio
5 kHz)
2.0 kV
(Repetitive ratio
5 kHz)
4.0 kV
(Repetitive ratio
2.5 kHz)
Special
Vibration
Continuous
vibration
1.0 m/s
2
or less 2.0 m/s
2
or less 4.9 m/s
2
or less
Brief vibration
(*2)
2.0 m/s
2
or less
(Seismic intensity
4 or less)
4.9 m/s
2
or less
(Seismic intensity
5 Upper or less)
9.8 m/s
2
or less
(Seismic intensity
6 Lower or less)
Transportation
vibration
Vertical:
4.9 m/s
2
or less
Horizontal:
2.9 m/s
2
or less
Vertical:
9.8 m/s
2
or less
Horizontal:
4.9 m/s
2
or less
Vertical:
19.6 m/s
2
or less
Horizontal:
9.8 m/s
2
or less
Transportation
impact
Vertical:
49 m/s
2
or less
Horizontal:
29.4 m/s
2
or less
Vertical:
98.1 m/s
2
or less
Horizontal:
49.0 m/s
2
or less
Vertical:
196.1 m/s
2
or less
Horizontal:
98.1 m/s
2
or less
Dust 0.1 mg/m
3
or less 0.3 mg/m
3
or less 10 mg/m
3
or less
Corrosive gas
Low temperature
and humidity
No gas detected.
(Evaluation point
9)
Relatively low
humidity Little gas
detected.
(Evaluation point
25)
Slightly high
humidity Little gas
detected.
(Evaluation point
36)
High temperature
and humidity
Some gases
detected.
(Evaluation point
50)
High temperature
and humidity A lot
of gases detected.
(51 Evaluation
point)
JEIDA-63-2000 : Industrial Information Processing and Control Equipment Installation Environment Standard
(Japan Electronics and Information Technorogy Industries)
*1: Immunity level based on direct contact discharge system
*2: The value enclosed in ( ) indicates the Japan Meteorological Agency Seismic Intensity Scale (reference value) estimated from
acceleration.
Class A: No effect on computer system (Difficult conditions for user to meet)
Class B: Office
Class S: Poor environment for computer system, worsening environment class S1→S2→S3
Oct. 22, 2007-00

Table of Contents