1. System Installation Requirements
1-10
TI 33Q01J10-01E
Installation Environment Specications
The following table lists environmental requirements for the installation of the CS 3000 system:
For environmental requirements for devices including PC and UPS, refer to their environmental
specifications.
SEE
ALSO
For details, refer to the hardware general specifications (GS) for each equipment.
Table Equipment Installation Specifications (1/2)
Item
Specifications
(LPCKIT)
Specifications
(YPCKIT, YAX101 and YAX801)
Temperature
Normal operation 5 to 40 °C
YPCKIT: 5 to 35 °C
YAX101, YAX801: 5 to 40 °C
Transportation/storage –20 to 60 °C –20 to 60 °C
Humidity
Normal operation 20 to 80 %RH 20 to 80 %RH
Transportation/storage 20 to 80 %RH 20 to 80 %RH
Temperature
fluctuation
Normal operation Within ±10 °C/h Within ±10 °C/h
Transportation/storage Within ±20 °C/h Within ±20 °C/h
Power
source
Voltage range
100-120 V AC ±10 %
220-240 V AC ±10 %
100-120 V AC ±10 %
220-240 V AC ±10 %
Frequency 50/60 ±3 Hz 50/60 ±3 Hz
Distortion factor 10 % or less 10 % or less
Peak value
125 V or larger (for 100-120 V)
275 V or larger (for 220-240 V)
125 V or larger (for 100-120 V)
275 V or larger (for 220-240 V)
Momentary failure 20 ms or less 20 ms or less
Withstanding voltage 1500 V AC/min. 1500 V AC/min.
Insulation resistance 20 M ohms/500 V DC
Grounding 100 ohms or less 100 ohms or less
Noise
Electric field
3 V/m or less (26 MHz to 1.0 GHz)
3 V/m or less (1.4 to 2.0 GHz)
1 V/m or less (2.0 to 2.7 GHz)
3 V/m or less (26 MHz to 1.0 GHz)
3 V/m or less (1.4 to 2.0 GHz)
1 V/m or less (2.0 to 2.7 GHz)
Magnetic field
30 A/m or less (AC)
400 A/m or less (DC)
30 A/m or less (AC)
400 A/m or less (DC)
Static electricity
4 kV or less (direct discharge)
8 kV or less (aerial discharge)
4 kV or less (direct discharge)
8 kV or less (aerial discharge)
Vibration
Vibration
Displacement amplitude:
0.25 mm or less (1 to 14 Hz)
Acceleration:
2.0 m/s
2
or less (14 to 100 Hz)
Displacement amplitude:
0.25 mm or less (1 to 14 Hz)
Acceleration: 2.0 m/s
2
or less
(14 to 100 Hz)
excl. LCD
Quake resistance 4.9 m/s
2
or less 4.9 m/s
2
or less excl. LCD
Vibration during
transportation
Horizontal: 2.9 m/s
2
or less
Vertical: 4.9 m/s
2
or less
Horizontal: 2.9 m/s
2
or less
Vertical: 4.9 m/s
2
or less
Impact Transportation impact
Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
Dust 0.3 mg/m
3
or less 0.3 mg/m
3
or less
Corrosive gas Class A, JEIDA-63 Class A, JEIDA-63
Note: The above specifications apply to a KIT only.