4.InstallationSpecications
4-3
TI 33J01J10-01EN
n Actual Power-On In-Rush Current of Each Component
Actual in-rush current data measured for each component is listed below:
Table System Equipment Power-On In-Rush Current
Model
In-Rush current (A) In-Rush current (A) In-Rush current (A)
100 V AC 220 V AC 24 V DC
Primary Secondary Primary Secondary Primary Secondary
  62 5 124 5 30 23
  62 5 124 5 30 23


(with Maximum no. of node units installed)
344 180 540 132 120 170


(with Maximum no. of node units installed)
344 180 540 132 120 170
  62 5 124 5 30 23


(19-inch rack mountable type)
62 5 124 5 30 23
  62 5 124 5 30 23
AVR10D Duplexed V net router 47 1 48 0.5 10 2
ACB51


344 180 540 132 120 170
 Node Unit for ESB Bus 62 5 124 5 30 23
 Optical ESB Bus Node Unit 62 5 124 5 30 23
AVR10D Duplexed V net Router 47 1 48 0.5 10 2
  47 1 48 0.5 10 2
A2NN10D Node Interface Unit 40 80 60
A2NN30D Node Interface Unit 40 80 60
 Power Supply Unit (100-240 V AC) 20 40
 Power Supply Unit (24 V DC) 30
 



are subject to change.
The power input circuit, with an in-rush current limiting circuit, restrains primary in-rush current,

lMeasurement Conditions

Power line impedance: Approx. 0.4 ohms (external line and internal impedance)
Turn-on timing: At 50 Hz, 90° or 5 ms after the AC zero-crossing point

Measurement: The primary peak and secondary peak are measured after turn-on.
lNote
 
 
󰀨
 

June 30, 2016-00

Table of Contents

Other manuals for YOKOGAWA CENTUM CS 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA CENTUM CS 3000 and is the answer not in the manual?

YOKOGAWA CENTUM CS 3000 Specifications

General IconGeneral
BrandYOKOGAWA
ModelCENTUM CS 3000
CategoryControl Systems
LanguageEnglish

Related product manuals