<4. Diagnostics>
4-10
IM 01C25T01-06EN
NOTE
When setting ILBD parameters in the transmitter
via “Online Parameter” of the EJX HART 5
DTM based on FDT1.2 menu, Diag Mode
automatically changes to 0 (Stop). After the
setting, Diag Mode automatically returns to the
original value.
NOTE
When setting ILBD parameters in the transmitter
via “Download to device” of the EJX HART 5
DTM based on FDT1.2 menu, Diag Mode
automatically changes to 0 (Stop).
Diag Period
The values such as Ratio fDP and BlkF are
averaged based on several hundreds of pressure
uctuation values in constant time. Diag Period
denes the sampling time is. The default value at
the shipment is set to 180 seconds.
Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu] Diag/Service
Diag Parameters → ILBD
Parameters Conguration →
Diag Period
EJX_HART 5[1.2]
DTM
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Diag Period
For the information on how to change the sampling
period, refer to subsection 4.2.2.10.
Diag Supp Count
When the value as Ratio fDP or BlkF exceeds
the threshold value for several times in a row,
it is estimated that the impulse line is plugged.
Diag Supp Count denes the number of times to
estimate blockage detection.
Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu] Diag/Service
Diag Parameters → ILBD
Parameters Conguration
Diag Supp Count →
EJX_HART 5[1.2]
DTM
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection Threshold
Diag Suppress Count →
If Diag Supp Count is set to three times, an
alarm is not generated at part ‘A in Figure 4.4.
Because the rst and second values only exceeded
consecutively the threshold.
When the value exceeds consecutively the
threshold value three times, an alarm is generated
(see part ‘B’ in Figure 4.4).
B
A
A
A
B BB
A
F0406.ai
Diag Supp Count (Number of times: 3)
Diag Supp Count (Number of times: 3)
Diag Period
Diag Period
Upper Threshold
(Ex.Lim fDPmax)
Lower Threshold
(Ex.Lim fDPmin)
An alarm is generated.
An alarm is generated.
Time
Time
Figure4.4 RelationshipofDiagSuppCountand
Alarm
The number of detection to give an alarm is set for
each blockage detection function. The default value
at the shipment is set to three times.
If uctuating around the threshold value, an alarm
may be often generated. In this case, change the
threshold value (Limit parameter) or the sampling
time (Diag Period) to enhance the accuracy of the
blockage detection. Refer to subsection 4.2.2.10.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA DPharp EJX***A Series and is the answer not in the manual?

YOKOGAWA DPharp EJX***A Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelDPharp EJX***A Series
CategoryTransmitter
LanguageEnglish

Related product manuals