C2-8
IM 34M06H62-02E 2nd Edition : June 2008-00
Figure C2.3 ON/OFF Control Operation Example (for reverse operation)
Manual Operation
In Manual mode, you can control the ON/OFF output manually by writing 100.0 or 0.0%
to the Manual Output (MOUT) parameter.
TIP
If you set MOUT to a value smaller than 0.0%, the value is treated as 0.0%. If the preset value is 0.1%
or larger, it is treated as 100.0%.
- The output limiter is disabled.
- The rate-of-change limit is disabled.