EasyManua.ls Logo

YOKOGAWA FX106 - Page 214

YOKOGAWA FX106
263 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12-2 IM 04L20A01-01E
Item Specifications
Filter FX103: Signal damping
On/off selectable for each channel
Time constant: selectable from 2, 5, and 10 seconds
FX106: Moving average
On/off selectable for each channel
Number of samples to be averaged is selectable from 2 to 16
FX112: Moving average
On/off selectable for each channel
Number of samples to be averaged is selectable from 2 to 16
Computation
Differential computation Between any two channels
Available for Volt, TC, RTD, and DI ranges.
Linear scaling Available for Volt, TC, RTD, and DI ranges.
Scaling limits: –30000 to 30000
Decimal point: user selectable
Engineering unit: user definable, up to 6 characters
Square root Square root computation and linear scaling
Available for Volt range.
Scaling limits: –30000 to 30000
Decimal point: user selectable
Engineering unit: user definable, up to 6 characters
12.1 Input Specifications

Table of Contents

Related product manuals