2-102
IM 04L51B01-17EN
All
All scan groups
1
Scan group 1
2
Scan group 2
Example When the measurement mode is dual interval,
apply a trigger to scan group 2.
OExecRec,1,2
Description
Manual trigger (p1 = 1) cannot be executed when the
advanced security function (/AS) is enabled.
If a manual sample is executed (p1 = 0) when there
are no source channels for manual sampling, a file
without any source channels will be created.
p2 is valid when multi batch is enabled and p1=3 or 4.
p2 is valid when the measurement mode is set to dual
interval and p1=1.
OExecSNTP
Queries the Time Using SNTP
Queries the time using SNTP.
Syntax
OExecSNTP,p1
p1
Time query execution (0)
Example Query the time using SNTP.
OExecSNTP,0
OMessage
Message Writing
Writes a message.
Write a Preset Message
Syntax
OMessage,p1,p2,p3,p4
p1
Action type (PRESET)
p2
Message number (1 to 100)
p3
Display group number
ALL
Write to all display groups
1 to 60 Write to specified groups
You can specify multiple groups at once.
To do so, separate display groups with a
colon.
p4
Batch group number (1 to the number
used)
Example Write the message in preset message number
8 to display groups 1 and 2.
OMessage,PRESET,8,1:2
Description
p4 is valid when multi batch is enabled. This cannot
be omitted.
Write a Free Message
Syntax
OMessage,p1,p2,p3,p4,p5
p1
Action type (FREE)
p2
Message number (1 to 10)
p3
Display group number
ALL
Write to all display groups
1 to 60 Write to specified groups
You can specify multiple groups at once.
To do so, separate display groups with a
colon.
P4
Message string to write (up to 32
characters, UTF-8)
p5
Batch group number (1 to the number
used)
Example Write a free message “MARK” as message
number 2 in display groups 3, 8, and 11.
OMessage,FREE,2,3:8:11,’MARK’
Description
p5 is valid when multi batch is enabled. This cannot
be omitted.
OPassword
Changes the Password
Changes the password.
Syntax
OPassword,p1,p2,p3
p1
Old password (up to 20 characters, ASCII)
p2
New password (up to 20 characters,
ASCII)
p3
New password (enter the same password
as p2)
Example Change the password from “PASS001” to
“WORD005.”
OPassword,’PASS001’,’WORD005’,’WO
RD005’
Description
For the characters that you can use for the password,
see Appendix 1.
OMath
Starts, Stops, or Resets Computation or
Clears the Computation Dropout Status
Display
Starts or stops computation, resets computed values, or
clears the computation dropout status display.
Syntax
OMath,p1,p2
p1
Action type (0)
0
Start computation
1
Stop computation
2
Reset computation
3
Clear the computation dropout
status display
p2 Batch group number
All
All math channels
1 to the
number
used
Math channel belonging to the
specified batch group
Query
OMath?
Example Start computation.
OMath,0
Description
You cannot use this command while the recorder is
saving or loading setup data.
2.6 Operation Commands

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA GX10 and is the answer not in the manual?

YOKOGAWA GX10 Specifications

General IconGeneral
BrandYOKOGAWA
ModelGX10
CategoryVoice Recorder
LanguageEnglish

Related product manuals