2-148
IM 04L51B01-17EN
2.10.23 Detail Event Log Output (FEventLog) (/AS)
The output in response to the command "FEventLog" is shown below. Output is possible
when the advanced security function (/AS) is enabled. Output from Web operation is
possible only when the GM’s advanced security function (/AS) is enabled.
Syntax
EA<crlf>
yyyy/mo/dd_hh:mm:ss_zzz_sss…s_uuu…u_ddd…<crlf>
…
EN<crlf>
yyyy/mo/dd_hh:mm:ss
Time of event occurrence
yyyy
Year (1900 to 2099)
mo
Month (01 to 12)
dd
Day (01 to 31)
hh
Hour (00 to 23)
mm
Minute (00 to 59)
ss
Second (00 to 59)
zzz
Event cause
KEY
Touchscreen operation, key operation
REM
Remote
COM
Ethernet communication
SER
Serial communication (RS-232, RS-
422/485, USB communication, or Bluetooth)
ACT
Event action
SYS
System
EXT
Operation from an external device (e.g.
Modbus)
WEB
Operation from web pages (GM, only when
the advanced security function (/AS) is
enabled)
sss…s
Event string (fixed to 16 characters. Unused character positions
are filled with spaces. See the table below.)
uuu…u
User name (fixed to 20 characters. Unused character positions
are filled with spaces.)
ddd…
Detailed information (see table below)
Event string, detailed information
Operations that are marked with an asterisk will be logged regardless of whether the
advanced security function is enabled or disabled.
All other operations are logged only when the advanced security function (/AS) is enabled.
Operation Event string ### information and detailed information
Information is
included in ###
Blue text indicates the detailed information output
format.
Error, system notification
Error occurrence Error### ### Error number (output in the event string)
Expiration Expiring## ## Schedule number
s•••
s••• Title
Example:
’Check Data’
Calibration operation
A/D calibration ExecA/DCal Unit:uu,Slot:ss
uu Unit
ss Slot
Module calibration CalModule Unit:uu,Slot:ss,m••
uu Unit
ss Slot
m Module name
Example:
Unit:00,Slot:01,GX90YA-04-C1
Login
2.10 ASCII Output Format