<7.GeneralSpecications>
7-7
IM 01C50G01-01EN
7.1.2 YTA610
PerformanceSpecications
Accuracy
HART communication type:
A/D accuracy/span + D/A accuracy
(See Table 7.3.)
Fieldbus communication type:
A/D accuracy (See Table 7.3.)
Cold Junction Compensation Accuracy
± 0.5°C 0.9 °F) for T/C only
Ambient Temperature Effect (per 10°C change)
See Table 7.4.
Stability
RTD: ±0.1% of reading or ±0.1°C per 2 years,
whichever is greater at 23±2°C.
T/C: ±0.1% of reading or ±0.1°C per year,
whichever is greater at 23±2°C.
5 Year Stability
RTD: ±0.25% of reading or ±0.25°C,
whichever is greater at 23±2°C.
T/C: ±0.5% of reading or ±0.5°C,
whichever is greater at 23±2°C.
Vibration Effect
The YTA610 is tested to the following
specications with no effect on performance per
IEC 60770-1
10 to 60 Hz 0.21 mm peak displacement
60 to 2000 Hz 3g
Power Supply Effect (HART Type)
±0.005% of calibrated span per volt
FunctionalSpecications
Input signals
Input number: single and dual input
Input type is selectable: Thermocouples, 2-, 3-,
and 4-wire RTDs, ohms and DC millivolts.
See Table 7.3.
Input signal source resistance (for T/C, mV)
1 or lower
Input lead wire resistance (for RTD, ohm)
10 Ω per wire or lower
Span & Range Limits
See Table 7.3.
Output signals
Two wire 4 to 20 mA DC Type
Output range: 3.68 to 20.8 mA
HART
®
protocol is superimposed on the 4
to 20 mA signal. Any single value among
followings can be selected as the analog
output signal.
Sensor 1, Terminal Temperature.
Dual input type, same as above plus;
Sensor 2, Average, and Differential
Temperature.
Also, up to three of the above values can
be displayed on LCD display or read via
communication.
Fieldbus communication Type
Output signal based on FOUNDATION
eldbus
TM
communication protocol.
Isolation
Input/Output/GND isolated to 500V DC
Except lightning protector option.
Manual Test Output Function
The output value can be set manually.
Sensor Burnout (HART Type)
High (21.6 mA DC) or Low (3.6 mA DC), user
selectable.
Output in Transmitter Failure (HART Type)
Down-scale: –5%, 3.2 mA DC or less , sensor
burnout –2.5%, 3.6 mA (Optional code C1)
Down-scale: –5%, 3.2 mA DC or less (Optional
code C2)
Up-scale: 110%, 21.6 mA DC or more
(Standard or Optional code C3)
Update Time (HART Type)
Approximately 0.5 seconds for a single sensor
(0.8 second for dual sensors) at damping time 0
Turn-on Time (HART Type)
Approximately 6 seconds for a single sensor (7
seconds for dual sensors)
Damping Time Constant
Selectable from 0 to 100 seconds
Self-Diagnostics
Self-diagnostic function based on the NAMUR
NE107 standard detects failures in the
hardware, conguration and communications.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA YTA610 and is the answer not in the manual?

YOKOGAWA YTA610 Specifications

General IconGeneral
BrandYOKOGAWA
ModelYTA610
CategoryTransmitter
LanguageEnglish

Related product manuals