<3. Part Names and Functions>
3-3
IM 01C50G01-01EN
(2) Process Variable Display
Process variables that can be displayed in YTA
are shown in the Table 3.2. A cycle of up to four
displays can be shown by assigning variables to the
parameters. Indicates values of process variables
with the indication limits –99999 to 99999.
F0303.ai
Table 3.2 Process Variable Display
HART BRAIN
Sensor1
Sensor1 Terminal
Terminal
Sensor2
Sensor2 Terminal
Sensor1 Sensor2
Sensor2 Sensor1
Sensor Average
Sensor Backup
PV PV
SV SV
TV TV
QV QV
% of RANGE % of RANGE
mA of RANGE mA of RANGE
3.4 Local Parameter Setting
WARNING
The local push button on the integral indicator
must not be used in a hazardous area. When it is
necessary to use the push button, operate it in a
non- hazardous location.
IMPORTANT
Do not turn off the power to the temperature
transmitter immediately after performing
parameter setting. Powering off within 30
seconds of performing this procedure will
return the parameter to its previous setting.
LCD update will be slower at low ambient
temperature, and it is recommended to use
LPS function at temperatures above −10
degrees C.
3.4.1 Local Parameter Setting (LPS)
Overview
Parameter conguration by the 3 push button
on the integral indicator offers easy and quick
setup for parameters of Tag number, Unit, PV
Damping, Display out 1, and etc. There is no
effect on measurement signal (analog output or
communication signal) when Local Parameter
Setting is carried out.
Table 3.3 Action
Action Operation
Activate Push or ▼ button
Move Push or button
Edit Push SET button
Save After parameter setting Push SET
button “SAVE?” → Push SET button →
“SAVED”
If “FAILED” appear, retry or check the
specicasions.
Cancel After parameter setting Push SET
button “SAVE?” → Push or ▼ button
“CANCL?” Push SET button
“CANCLD”
Abort Hold down the SET button for over 2
seconds “ABORT” and move to the
process measurement display
Exit Push button (When the rst parameter is
selected)
or
Push button (When the last parameter is
selected)
Time out no operation for 10 minutes