JOHNSON CONTROLS
148
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
tor support. The “Horizontal” designation refers to the 
proximity probe installed at approximately 45 degrees 
from the vertical center on the right side of the rotor 
support when facing the shaft end of the compressor. 
The “Vertical” designation refers to the proximity 
probe installed at approximately 45 degrees from the 
vertical center on the left side when facing the shaft 
end of the compressor. When the sensors are enabled, 
the following messages are also enabled:
After the accelerometer cables are con-
nected to the transmitters, the zero on all 
vibration transmitters must be adjusted 
to provide a 4.0 mA output to ensure the 
proper operation of these messages.
“Compressor Horizontal Vibration Out Of 
Range”
The input signal from the Compressor Horizontal Vi-
bration Transmitter is more than 0.5 mA below the 
calibrated minimum input signal, which generally in-
dicates a defective transmitter, accelerometer, or cable. 
The chiller can only be started after the transmitter 
input is within the calibrated range and the START/
STOP control switch is placed in the STOP-RESET 
(O) position. 
An input signal above 2.0 In/Sec would 
also indicate a defective transmitter or 
accelerometer but will generate a normal 
safety shutdown message since this value 
exceeds the safety setpoint.
“Compressor Vertical Vibration Out Of 
Range”
The input signal from the Compressor Vertical Vibra-
tion Transmitter is more than 0.5 mA below the cali-
brated minimum input signal, which generally indicates 
a defective transmitter, probe, or cable. The chiller can 
only be started after the transmitter input is within the 
calibrated range and the START/STOP control switch 
is placed in the STOP-RESET (O) position.
“Compressor - Horizontal Vibration”
The input signal from the Compressor Horizontal Vi-
bration Transmitter is above the CVSP2-Compressor 
Vibration Shutdown setpoint shown on the Alarm/
Shutdown Setpoints Screen. This check is bypassed 
during shutdown until the start sequence is initiated. 
The START/STOP control switch must be placed in the 
STOP-RESET (O) position before starting the chiller.
“Warning - Compressor - Vertical  
Vibration”
The input signal from the Compressor Vertical Vi-
bration Transmitter is above the CVSP2-Compressor 
Vibration Shutdown setpoint shown on the Alarm/
Shutdown Setpoints Screen. This check is bypassed 
during shutdown until the start sequence is initiated. 
The START/STOP control switch must be placed in the 
STOP-RESET (O) position before starting the chiller.