JOHNSON CONTROLS
55
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
2
Pump #2 Run Output (LED)
Illuminates when the Vacuum Pump #2 contactor is 
energized to start the pump. This will occur after the 
Vacuum Pump #2 Sealing Water Flow Switch status 
changes to closed. This object only appears if MSSP11-
Vacuum Pump Mode is set for Dual on Configuration 
Screen 1.
Pump #2 Aux Contact (Open/Closed)
Displays the status of the auxiliary contact on the 
Vacuum Pump #2 contactor. The status will change 
from Open to Closed after the Run Output LED 
illuminates indicating that the contactor has pulled in. 
This object only appears if MSSP11-Vacuum Pump 
Mode is set for Dual on Configuration Screen 1.
PROGRAMMABLE
Pump Mode (Auto/Manual 1/ Manual 2)
Access Level Required: SERVICE
This key initiates a Manual start sequence for the 
selected vacuum pump by manually energizing the 
associated vacuum pump sealing water solenoid 
valve. The selected vacuum pump will start after the 
associated sealing water flow switch status changes 
to closed. The manual starting of the selected pump 
will only be initiated if the other pump is not running. 
If MSSP11-Vacuum Pump Mode is set for Single 
on Configuration Screen 1, the vacuum pump start 
sequence will be initiated if Manual 1 or Manual 2 is 
selected. 
NAVIGATION
Home
Access Level Required: VIEW 
Causes an instant return to the Home Screen. 
System
Access Level Required: VIEW
Causes an instant return to the Steam System Screen.