SECTION 6 - PRINTING
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
6
FIGURE 53 - SAMPLE PRINTOUT (SETPOINTS)
LD26760
YORK Setpoints
¬Sales Order Job Name here
Sales Order Model Number here
Sales Order Serial Number here
Sales Order Compressor Model here
Sales Order Evaporator Model here
Sales Order Condenser Model here
Sales Order VSD Model here
YZ ¬Chiller ID 1
(c) 2010 Johnson Controls
Mon 01 Nov 2010 9:25:18 AM
Software Versions
------------------------------------------------------
Controls = Y.OPT.1.05.308
CC = 3.09
BIOS = C.OPT.00.02
Kernel = 1.20
GP = 1.09
GUI = 0.43
SIO = 1.25
GPIC = 0.14
Ext I/O = C.EXP.01.00
VSD Inverter = C.H035.04.01.02
VSD Modbus = 05.01
System Information
------------------------------------------------------
Data Display Mode = English
System Language = English
Date Format = DD MMM YYYY
Control Source = Local
Remote Analog Input Range = 0-10 Volts
Line Voltage = 460V
Line Frequency = 60Hz
Chilled Liquid Pump Operation = Standard
Head Pressure Control = Disabled
Hot Gas Bypass = Enabled
Flow Switch Input = J14
Power Failure Restart = Auto
Clock = Enabled
Jumper Settings
------------------------------------------------------
Liquid Type = Water
Refrigerant Selection = R134a
Printer Setup
------------------------------------------------------
Automatic Printer Logging = Disabled
Log Start Time = 12:00 AM
Output Interval = 60 Min
Printer Type = Okidata
Baud = 9600 Baud
Data Bits = 8 Bits
Parity = None
Stop Bits = 1 Bit
COM 2 Setup
------------------------------------------------------
Baud = 38400 Baud
Data Bits = 8 Bits
Parity = None
Stop Bits = 2 Bits
Evaporator
------------------------------------------------------
Leaving Chilled Local Setpoint = 42.0 ~F
Leaving Chilled ISN Setpoint = 45.0 ~F
Leaving Chilled Modem Setpoint = 45.0 ~F
Leaving Chilled Analog Setpoint = 42.0 ~F
Leaving Chilled Digital Setpoint = 42.0 ~F
Remote Range = 10.0 ~F
Restart Offset = 4.0 ~F
Restart Temperature = 46.0 ~F
Shutdown Offset = 6.0 ~F
Shutdown Temperature = 36.0 ~F
Brine Low Evaporator Cutout = 25.0 PSIG
Smart Freeze = Off
Refrigerant = Disabled
Condenser
------------------------------------------------------
High Pressure Warning Threshold = 162.5
PSIGHead Pressure Control = Enabled
Head Pressure Setpoint = 23.0 PSID
(when HPC is Enabled)
Type = 0-10V
(when HPC is Enabled)
PID Output = Direct
(when HPC is Enabled)
Minimum PID Output = 0.0 %
(when HPC is Enabled)
Shutdown Position = 0.0 %
(when HPC is Enabled)
Head Pressure Control P = 2.00
(when HPC is Enabled)
Head Pressure Control I = 2.00
(when HPC is Enabled)
Head Pressure Control D = 0.00
(when HPC is Enabled)
Isolation Valves = Enabled
Surge
------------------------------------------------------
Surge Sensitivity = 0.3
Shutdown = Enabled
Count Limit = 15
Count Window = 3 Min
Condenser Refrigerant Level Control
------------------------------------------------------
Condenser Level Setpoint = 50.0 %
Condenser Level Control Startup Position = 25.0 %
Condenser Level Control Startup Delay = 15 Sec
Condenser Level Control Ramp Time = 1 Min
Condenser Level Control Kp = 0.50
Condenser Level Control Ti = 100.0
Condenser Level Control Td = 0.00