York YZ MODEL A - Master Slot Numbers List for Use with Trend Feature

York YZ MODEL A
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
87
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
3
MASTER SLOT NUMBERS LIST FOR USE WITH TREND FEATURE
SLOT # DESCRIPTION
SYSTEM
256 Chiller Operating State
259 Safety Relay
260 Cycling Relay
261 Warning Relay
262 Operating Hours
264 Number Of Starts
267 Remote Ready To Start
1925 Local Run Command
EVAPORATOR
1792 Leaving Chilled Liquid Temperature
1793 Temperature Differential
1794 Chilled Liquid Flow Switch
1795 Chilled Liquid Pump
1807 Entering Chilled Liquid Temperature
1808 Evaporator Pressure
1809 Evaporator Saturation Temperature
1810 Evaporator Small Temp Difference
1812 Evaporator Refrigerant Temperature
1813 Active LCHLT Setpoint
CONDENSER
2048 Leaving Condenser Liquid Temperature
2049 Condenser Liquid Flow Switch
2050 Condenser Liquid Pump
2051 Entering Condenser Liquid Temperature
2052 Condenser Pressure
2053 Condenser Saturation Temperature
2054 Condenser Small Temperature Difference
2056 Condenser Refrigerant Temperature
2057 High Pressure Switch
2059 Subcooling Temperature
2061 Drop Leg Refrigerant Temperature
2056 Condenser Refrigerant Temperature
COMPRESSOR
1296 Discharge Temperature
1299 Discharge Superheat
17748 Discharge Superheat Limiting Allowed
17750 Discharge Superheat Limit Threshold
18397 Adjusted Discharge Superheat
HOT GAS
8231 HGBP COMMAND
SLOT # DESCRIPTION
SURGE
8236 ACC Surge Detected
8238 Surge Avoidance Count
8319 Surge Avoidance Surge Detected
CONDENSER REFRIGERANT LEVEL CONTROL
8206 Condenser Refrigerant Level
17715 Condenser Active Level Setpoint
17716 Condenser Level Control State
17718 Condenser Level Control Valve Command
2072 Subcooler Effectiveness
VARIABLE GEOMETRY DIFFUSER
8354 VGD Shutdown Command
8355 VGD Fault Code
8358 Stroke Calibration Complete
8359 VGD Stroke Calibration Command
17408 Discharge Pressure
18135 Mach Number
VARIABLE SPEED DRIVE
2305 Motor Run
3047 VSD Fault
20823 Input % Full Load Amps
2306 Motor % Full Load Amps
2818 Input Power
2819 kW Hours
2820 DC Bus Voltage
2821 DC Inverter Link Current
2822 Output Frequency
2823 Output Voltage
2824 Phase A Output Current
2825 Phase B Output Current
2826 Phase C Output Current
2828 Trigger SCR Output
2829 Water Pump Output
2833 Internal Ambient Temperature
2834 Converter Heatsink Temperature
2835 Phase A Heatsink Temperature
2836 Phase B Heatsink Temperature
2837 Phase C Heatsink Temperature
3047 VSD Fault