EasyManua.ls Logo

York YZ MODEL A - Page 14

York YZ MODEL A
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
14
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
SECTION 1 - SYSTEM FUNDAMENTALS
The graphic display can display data in either English
or Metric mode.
English (temperatures in °F and pressures in
PSIA)
Metric (temperatures in °C and pressures in kPa)
The control center continually monitors system opera-
tions. Operators are advised of chiller conditions by
use of various status and warning messages. This data
is recorded and preserved in memory even through a
power failure. Operational data, warnings and shut-
down messages may be viewed at any time.
In addition, the control center may use alarms to no-
tify the user of certain conditions. A complete listing of
shutdown, status, and warning messages is listed in the
Display Messages on page 90 of this manual.
The control center includes capabilities for remote con-
trol and communications. Common networking proto-
col through the Building Automation System (BAS) al-
lows increased remote control of the chiller, as well as
24-hour performance monitoring via a remote site. An
optional circuit board called the SC-EQUIP provides
Johnson Controls and YORK mechanical equipment
such as the YZ chiller with building automation system
(BAS) networking connectivity.
The chiller also maintains standard digital remote ca-
pabilities. Both of these remote control capabilities al-
low for the following standard Energy Management
System (EMS) interfaces. The actual connection de-
tails are in the Field Connections section of the Wiring
Diagram (Form 161.01-PW1 and PW3):
Remote Start
Remote Stop
Remote Leaving Chilled Liquid Temperature
Setpoint adjustment: BAS coms, Analog signal,
(0-10VDC or 4-20mA) or Pulse Width Modula-
tion
Remote Current Limit Setpoint adjustment: BAS
coms, Analog signal, (0-10VDC or 4-20mA) or
Pulse Width Modulation
Remote “Ready to Start” Contacts
Safety Shutdown Contacts
Cycling Shutdown Contacts
The OptiView panel can be used to control the cus-
tomer chilled and condenser liquid flow. A set of con-
tacts exists to initiate flow for each shell. Details are in
the Field Connections section of the Wiring Diagram
(Form 161.01-PW2 and PW4). The chilled water pump
contacts close immediately upon execution of a chiller
start command. They open coincident with the receipt
of a stop command or a fault other than those below:
A. LEAVING CHILLED LIQUID - LOW TEM-
PERATURE cycling shutdown.
B. MULTIUNIT CYCLING - CONTACTS OPEN
or SYSTEM CYCLING - CONTACTS OPEN
(Only if Chilled Liquid Pump Operation is set to
ENHANCED)
C. LEAVING CHILLED LIQUID FLOW SWITCH
OPEN cycling shutdown
The Condenser Pump contacts close immediately upon
execution of a chiller start command. They open coin-
cident with receipt of a chiller stop command or fault
other than CONDENSER-FLOW SWITCH OPEN cy-
cling shutdown.
If the chiller is stopped and the condenser pump con-
tacts are open (flow off), the contacts close when satu-
rated condenser temperature is less than 35.0 °F (1.67
°C). This helps mitigate condenser freeze due to plant
issues in brine applications.
If the contacts are closed only due to the saturated con-
denser temperature, they are opened when saturated
condenser temperature returns above 40.0 °F (4.44
°C). If the existing logic calls for them to be closed,
they remain closed.
Some screens, displayed values, programmable
setpoints and manual controls exist for service techni-
cian use only. They are only displayed when logged in
at SERVICE access level or higher. These parameters
affect chiller operation and should never be modified
by anyone other than a qualified service technician.
The chiller operating program resides in the Opti-
View Control Center microboard. Software versions
(Y.OPT.01.xx.yzz) are alpha-numeric codes that rep-
resent the application, language package and revision
levels as follows.

Table of Contents

Related product manuals