JOHNSON CONTROLS
46
FORM 161.01-OM1
ISSUE DATE: 6/8/2018
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
DISPLAY ONLY FIELDS
FIELD/LED NAME DESCRIPTION
Std Dev
Displays the Standard Deviation of the Radial Bearing J in the X and Y axis,
Thrust Bearing H and the Radial Bearing K in the X and Y axis expressed in
Mils.
Peak Vibration
Displays the Peak Vibration of the Radial Bearing J, Thrust Bearing H and the
Radial Bearing K expressed in Mils.
Avg Gap Change
Displays the Average Gap Change of the Radial Bearing J and the Radial Bear-
ing K expressed
in Mils.
Avg Force
Displays a running 1 second Average Force of the Radial Bearing J in the X
and Y axis, Thrust Bearing H and the Radial Bearing K in the X and Y axis.
Expressed in lbs or Nm.
J1, J2, J3, J4 (Current)
Displays the four magnetizing currents for the impeller end bearing expressed in
Amps.
H1, H2 (Current) Displays the two magnetizing currents for the thrust bearing expressed in Amps.
K1, K2, K3, K4 (Current)
Displays the four magnetizing currents for the drive end bearing expressed in
Amps.
MBC Command
Displays the OptiView state command to the MBC. (Delevitate, Levitate or Cali-
brate).
MBC Control Mode
Indicates the MBC Control Mode. (Delevitated, Levitated, Calibrating J, Calibrat-
ing K or Calibrating H).
NAVIGATION
NAVIGATION
BUTTON DESCRIPTION
Home Causes immediate return to the Home Screen.
Compressor Causes immediate transfer to the Compressor Screen.