Smart Connect Single Loop Touch Screen Panel
Doc: GLT-229-7-1 8
Issue: 3
Date: 12/05/2017
2.3 PANEL SPECIFICATIONS - ENCLOSURE
ENCLOSURE SIZE (L x W x D mm)
2.4 PANEL SPECIFICATIONS - ELECTRICAL
2 x 12V SLA (27.6V DC @ 20 C) (3Ah – 7Ah)
NON-INTEGRAL (SWITCH MODE)
DC OUTPUT: Vmax = 31V ,Vmin = 19.5V
I max A: 4.1 A
Ripple & Noise: <= 0.6V
Vmax = 31.5V, Vmin = 19.5V
End-of-Line Resistance: 4k7ohm 0.25W
Trigger value: 2k7 ohm
CONVENTIONAL SOUNDER OUTPUT (x2)
I max: 100mA
Quiescent voltage: -5 to -9V DC
Active voltage: 18 to 28V DC
End-of-Line Resistance: 4k7 ohm 0.25W
(C,NO,NC)
Contact rating: 230V AC @ 1A
Normally Energised (C,NO,NC)
Contact rating: 230V AC @ 1A
35V Nominal (Vmax 39 V DC Vmin 24 V DC)
44 ohm (22 ohms + to +, 22 ohms – to -)
MAXIMUM DISTANCE BETWEEN NODES
1 km with screened Data cable
4.3” Resistive touch screen. 480 x 272 pixel resolution
Fire Zones 1 – 16
Fault / Disable / Test Zones 1 - 16
Power
Common Fire
Sounder Delay On
General Disablement
Controls active
System Fault
Common Fault
Sounder Fault / Disablement
General Test
Sounder Active
Start Sounders
Stop Sounders
Silence Buzzer
Reset
(All other controls via touch screen)
Temperature: -5 to 40 C
Relative Humidity: 95% Non-Condensing
will withstand vibrations between 5 & 150 Hz
USB
RS485 for network
TCP/IP
Micro SD card (for future use)
EN 54-2 Optional Functions with Requirements
7.8, 7.11,7.12, 8.3, 9.5, 10