73Technical data
EN
10.2 Cable specifications
EVSE Terra 60 Terra 360
AC Input
AC cable cross section
150 mm
2
(recommend)
2 x 240 mm
2
(recommend)
AC connection type M10 cable lug M12 cable lug
AC cable diameter (cable entry plate) 27...35 mm Max. 34 mm
Protective Earth (PE)
PE cable cross section At least half of the phase cable cross section
PE connection type M10 cable lug
PE cable diameter (cable entry plate) 19...28 mm 27...35 mm
PE connection point 2 on the PE busbar
Ethernet
CAT
CAT 5e (recommend)
CAT 6 (high presence of electromagnetic
interference and/or noise)
Ethernet cable diameter (cable entry plate) 8...13 mm 19...28 mm
Tilt sensor (option)
Number of wires
4 (2 wires for power supply and 2 wires for relay
contacts)
Max. Wires cross section 4mm
2
Diameter outside
Cable diameter accepted by cable gland:
19...28 mm
Conductor Fine strand copper wire
Insultation
PVC or other material that is serviceable for
outdoor use and UV-protected
Voltage rating 600 V
10.3 Torque specification
EVSE Terra 60 Terra 360
Parameter Specification [Nm] Specification [Nm]
Fasteners for the PE wire 50...55
Fasteners for the L1, L2, L3 (neutral wire Terra 60) 30...44 50...75
Fasteners for the connection of the EVSE to the base
(M12 bolt)
10
Tilt sensor screw terminal block 3