2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
49
Special Volume measurement setting
Process info Device parameter to be configured
TAG PD_TAG
 
 
Calibration Unit PRTB_PRIMARY_VALUE_RANGE _UNIT
Linearization Type QUATERNARY_VALUE_LIN_TYPE Linear
Cylindrical lying container
Spherical container
 
 
Output Scale Unit 



Further common setting
Process info Device parameter to be configured
Node Address
Damping 
Critical Limit Low 
Advisory Limit Low 
Advisory Limit High 
Critical Limit High 
Alarm Hysteresis 
IMPORTANT
No field calibration is normally requested, the transmitter has been trimmed to the calibration points (URV and LRV) to
provide the best performances in the real operating range.
IMPORTANT
In case the calibrated range must be changed, please refer to the dedicated section of this manual.