48
2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
...Device Configuration/Setting through FF communication
Special Flow measurement setting
Process info Device parameter to be configured
TAG PD_TAG
 
 
Calibration Unit PRTB_PRIMARY_VALUE_RANGE _UNIT
Linearization Type QUATERNARY_VALUE_LIN_TYPE Square Root
Bidirectional Flow
 
 
Output Scale Unit 
Linear Volume measurement setting
Process info Device parameter to be configured
TAG PD_TAG
  
  
Calibration Unit PRTB_PRIMARY_VALUE_RANGE _UNIT 
Linearization Type 
 
 
Output Scale Unit