2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
47
User settings
Generally, the 266 PdP pressure transmitters are delivered pre-configured on as per purchase order request, suitable in order to 
measure Pressure, Level, Flow or Volume. For the device configuration it is necessary to know at least the following process info as 
minimum:
•  TAG
•  Calibration Range/Scale and its engineering unit as range of pressure to be measured in input
•  Output Range/Scale and its engineering unit
The Linearization Type could be both, directly communicated by the client, or identified in the factory, depending by the 
engineering unit of the of the Output Scale.
For some measurements, the linearization type is set inside the AI block (Aix_L_TYPE) while, for more complex measurements, the 
Linearization type must to be set inside the Pressure Transducer Block (PTRB_QUATERNARY_VALUE LIN_TYPE).
Pressure and Level measurement setting
Process info Device parameter to be configured
TAG PD_TAG
 
 
Calibration Unit PRTB_PRIMARY_VALUE_RANGE _UNIT 
Linearization Type 
 
 
Output Scale Unit 
Normal Flow measurement setting
Process info Device parameter to be configured
TAG PD_TAG
  
 
Calibration Unit PRTB_PRIMARY_VALUE_RANGE _UNIT 
Linearization Type 
 
 
Output Scale Unit