52
2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
...Block Mapping
Idx Parameter Description / Range / Selections / Notes
RESTART
Uninitialized
Run
Restart resource
Restart with default
Restart process
Special Restart
Special Operations
FEATURES Used to show supported resource block options
FEATURES_SEL
Reports Supported
Fault State Supported
SW Write Lock Supported
HW Write Lock Supported
Multi-bit Alarm (Bit-Alarm) Support
CYCLE_TYPE Identifies the block execution methods for this resource
CYCLE_SEL
Bit 1 Scheduled
Used to select the block execution methods for this
resource.
Completion of block
execution
MIN_CYCLE_T Time duration of the shorted cycle interval of which the resource is capable.
MEMORY_SIZE Available configuration memory in the empty resource. To be checked before attempting a download
NV_CYCLE_TIME
Minimum time interval for writing copies of NV parameters to non-volatile memory. Zero means it will be never
automatically copied.
FREE_SPACE Percent of memory available for further configuration. Zero in a preconfigured device
FREE_TIME Percent of the block processing time that is free to process additional blocks.
SHED_RCAS
Time duration at which to give up on computer writes to function block Rcas locations. Shed from Rcas shall never
SHED_ROUT
Time duration at which to give up on computer writes to function block Rout locations. Shed from Rout shall never
FAULT_STATE Fault State
SET_ FSTATE Set Fault State
CLR_FSTATE Clear Fault State
MAX_NOTIFY Maximum number of unconfirmed alert notify messages possible
LIM_NOTIFY Maximum number of unconfirmed alert notify messages allowed
CONFIRM_TIME
WRITE_LOCK
1 Unlocked (default),
Locked
If locked is selected, no writes are allowed except than
Unlock.
Block inputs will continue to be updated
UPDATE_EVT This alert is generated by any change to the static data
BLOCK_ALM
"The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The first alert to become active will set the Active Status in the
status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active Status, if the subcode has changed"
ALARM_SUM The alert status associated to the function block
ACK_OPTION
0 Auto Ack Disabled (default)
Selection of whether alarms associated the function block
will be automatically acknowledged
Auto Ack Enabled
WRITE_PRI Priority of the alarm generated by clearing the write_lock
WRITE_ALM This alert is generated if the write_lock parameter is cleared
ITK_VER
Major revision number of the Interoperability test case used in certifying this device as interoperable. See the ITK
https://www.fieldcommgroup.org/registered-products
CB_SW_REV