2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
53
Idx Parameter Description / Range / Selections / Notes
CB_HW_REV
CAPABILITY_LEV Not Supported
COMPATIBILITY_REV
FD_VER
FD_FAIL_ACTIVE Active error conditions mapped as Failure
According to the NAMUR NE107 Categories.
It is bit string, and multiple conditions may be shown.
SEE its bit MAPPING DETAIL in the dedicated section
FD_OFFSPEC_ACTIVE Active error conditions mapped as Out of Specification
FD_MAINT_ACTIVE Active error conditions mapped as Maintenance
FD_CHECK_ACTIVE Active error conditions mapped as Check Function
FD_FAIL_MAP Errors Mapped as Failure
Default mapping:
Bit 1 Static Pressure Sensor failure
Bit 2 Sensor Temperature failure
Bit 3 Pressure or Diff.Pressure Sensor failure
Bit 4 Pressure or Diff.Pressure Out of Sensor limits
Bit 5 Static Pressure Out of Sensor Limits
Bit 11 Pressure Over-range
Bit 12 Sensor Signal not Valid
Bit 14 Sensor memory fail
Bit 17 Electronic memory fail
FD_OFFSPEC_MAP Errors Mapped as Out of Spec
Default mapping:
Bit 6 Sensor Temperature Out of the Operating Limits
Bit 10 Primary Variable Out of Range
FD_MAINT_MAP Errors Mapped as Maintenance:
Default Mapping:
Bit 7 Replace operation required
Bit 8 PILD output condition detected
Bit 9 PILD operating condition has changed. New PILD
training is required
Bit 14 Sensor Non-Volatile memory write error
Bit 15 Electronic Interface error with the connected sensor
Bit 17 Electronic Non-Volatile memory write error
Bit 19 Max.Working pressure limit has been exceeded
FD_CHECK_MAP Errors Mapped as Check Function
Default Mapping:
Bit 0 Function Check
Bit 18 Input simulation active
FD_FAIL_MASK Fail error to be masked
Default no error masked
FD_OFFSPEC_MASK Out of Spec errors to be masked
FD_MAINT_MASK Maintenance errors to be masked
FD_CHECK_MASK Function Check errors to be masked
FD_FAIL_ALM Fail Alarm Object
FD_OFFSPEC_ALM Out of Spec Alarm Object
FD_MAINT_ALM Maintenance Alarm Object
FD_CHECK_ALM Function Check Alarm Object
FD_FAIL_PRI Fail error priority
FD_OFFSPEC_PRI Out of Spec error priority
FD_MAINT_PRI Maintenance error priority
FD_CHECK_PRI Function Check error priority
FD_SIMULATE
1: Disabled
Default
2
: Active
FD_RECOMMEN_ACT
Numeric Code defining the corrective action to be taken for the problem solution. When the Device’s DD has been
imported in the Hosts it converts the numeric code into a Textual info comprehensible for the user
EXTENDED_ACTIVE
Some of the Active Errors of Fail, Maint, Out of Spec, Function Check classification could be produced by more root
causes that can be seen by reading this parameter. SEE its bit MAPPING DETAIL in the dedicated section
DIAGNOSIS_HISTORY
The bit associated at each error condition is permanently set after the condition became set at least one time Its bit
mapping is the same as for x_ACTIVE. SEE its bit MAPPING DETAIL in the dedicated section