2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
59
The differential pressure generated by the flow primary is for the maximum flow rate 2500 mmH2O, for the max reverse flow rate 
2500 mmH2O.
The transmitter will have to be configured as follows:
Calibrated span:    LRV       = -2500mmH2O
   URV    = 2500mmH2O
      Linearization Type  = Bidirectional flow
Once configured as above the transmitter will deliver:
      flowrate 100 lt/hr reverse: output= 0%
   no flowrate:   output= 50%
      Flow rate 100 lt/h:   output= 100%
Cylindric lying tank
This function is used to measure the volumetric level into a cylindrical horizontal tank with flat ends. The transmitter calculates the 
volume from the measured filling level.
Spherical Tank
This function is used to measure the volumetric level into a spherical tank. The transmitter calculates the volume from the 
measured filling level.
Block Mapping
Idx Parameter Description / Range / Selections / Notes
 BLOCK_OBJ
In the Block Object data structure, there are different items describing the block characteristics. Execution period, 
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
 ST_REV
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a 
static parameter value (S – under Storage) in the block is changed.
 TAG_ DESC The user description of the intended application of the block
 STRATEGY The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
 ALERT_KEY The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
 MODE_BLK
TARGET AUTO / OOS The selectable modes by the operator.
ACTUAL The mode the block is currently in.
PERMITTED AUTO / OOS Allowed modes that the target may take on
NORMAL AUTO The common mode for the Actual.
 BLOCK_ERR
This parameter reflects the error status associated with the hardware or software components associated with a 
block. It is a bit string, so that multiple errors may be shown.
 UPDATE_EVT This alert is generated by any change to the static data
 BLOCK_ALM
The block alarm is used for all configuration, hardware, and connection failure or system problems in the block.
The cause of the alert is entered in the sub-code field. The first alert to become active will set the Active Status in the 
status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be 
reported without clearing the Active Status, if the sub-code has changed
 TRANSDUCER_DIRECTORY Directory that specifies the number and starting indices of the transducers in the transducer block
 TRANSDUCER_TYPE Identifies the transducer type. 100 = Standard Pressure with calibration
 TRANSDUCER TYPE VERSION
the transducer specification on which the transducer is based, and BB is a revision number assigned and controlled 
by the manufacturer of the device.
 XD_ERROR Transducer block error sub-code
 COLLECTION_DIRECTORY
Directory that specifies the number, starting index, and the DD items IDs of the data collections in each transducer 
within a transducer block
 PRIMARY_VALUE_TYPE Selects the type of measurement represented in PRIMARY_VALUE. Changing has no calculation effect