2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
69
Idx Parameter Description / Range / Selections / Notes
 PILD_TRAIN_OUTPUT
This parameter gives information on
the status of the training phase
 PILD Train Not Done Training not yet executed
 PILD Train OK Training correct
 PILD Train Frequency Tuning
The training phase is checking the signal
frequency for its execution
 PILD Train Power Instable
Signal power has passed the max.
allowed deviation This process condition
is considered instable for a good training
 PILD Train Pressure Instable
Pressure has passed the max.allowed
deviation. This process condition is
considered instable for a good training
 PILD Train Low Noise
The Noise of the process is too low for
allowing a good training
 not used
 not used
 PILD_SENSITIVITY Algorithm sensibility
 LOWEST
 VERY LOW
 LOW
 MEDIUM (Default)
 HIGH
 VERY HIGH
 HIGHEST

PILD_BAND_
AUTOTUNING
PILD auto tuning enable/disable
No Doesn’t perform auto tune (default
value)
Yes Performs Auto Tune
 PILD_BAND_LO

 PILD_BAND_HI
 PWR_ON_CNT
Power On Counter. Number of the device Power on
 TOT_WORK_TIME
Total Working hours. Total amount of time the transmitter has been kept
switched on

PAR_WORK_TIME
Partial Working hours. Partial amount of time the transmitter has been
switched on.
The user can clear this counter
 MAX_PdP_VALUE
Max Historical Sensor value
Resettable from RESET_MIN_MAX_VALUE
 MIN_PdP_VALUE
Min Historical Sensor value
 MAX_SENS_TEMP_VAL
Max Historical temp. value
 MIN_SENS_TEMP_VAL
Min Historical temp. value
 MA X_ STATIC_PRESS _VAL
Max Historical Static Press value
 MIN_STATIC_PRESS_VAL
Min Historical Static Press value
 SERVICE_MAX_PdP_VALUE
For service Use. Max Historical Sensor value
Resettable from RESET_SERV_MIN_MAX_VALUE
 SERVICE_MIN_PdP_VALUE
For service Use. Min Historical Sensor value
 SERV_MAX_SENS_TEMP_VAL
For service Use. Max Historical temp. value
 SERV_MIN_SENS_TEMP_VAL
For service Use. Min Historical temp. value
 SERV_MAX_STATIC_PRESS_VAL
For service Use. Max Historical Static Press
value
 SERV_MIN_STATIC_PRESS_VAL
For service Use. Min Historical Static Press
value
 RESET_MIN_MAX_VALUE
Reset the selected User Min Max
values
None
Reset PdP Values
Reset Sensor Temperature
Values
Reset Static Pressure Values