2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
75
Cat. Error
RB_fail / maintenance / offspec / check_
ACTIVE (indexes 47, 48, 49, 50)
RB_EXTENDED_ACTIVE (index 69)
Function Check
PRTB NormalMode = AUTO and PRTB
TargetMode != AUTO
Sensor Invalid
The transducer is not able to generate a
valid signal due to one of the following
conditions (see RB_EXTENDED_ACTIVE)
The primary signal of the sensor is no longer
available
Sensor Memory Fail
The data in the sensor memory are
corrupted precluding the correct
functionality of the device
The sensor and the connected electronics are
incompatible
Memory Failure
The device data loaded at the start up are
corrupted precluding the correct
functionality of the device
P-dP Sensor Fail
The sensor signal value is incorrect due to a
mechanical failure i.e. Loss of fill fluid from
the cell; ruptured diaphragm, broken
sensor…
Static Pressure Sensor Fail
The sensor signal value is incorrect due to a
mechanical failure i.e. The circuitry for the
sampling of the static pressure has failed...
Valid for Differential pressure models
Sensor Temperature Fail
The circuitry for the sampling of the
temperature has failed. The measurement
accuracy is decreased more than the
acceptable error
Pressure Overrange
The Pressure is outside the overpressure
limit and risk to damage the sensor
P-dP Out Of Limit
The measured Process Pressure is outside
the sensor limits and no longer representing
the true applied process value
Static Pressure Out Of Limit
The measured Static pressure is above its
operational limit
Input Simulation Active
The Input Simulation function is Active At
least one of these variables is simulated
The Pressure Value produced in output is
calculated starting from a simulated input
The Static Pressure Value produced in output is
calculated starting from a simulated input
The Sensor Temp Value produced in output is
calculated starting from a simulated input
Sensor Temperature Out Of
Limit
The measured sensor temperature is
outside of its operational limits
Max. Working Pressure
Exceeded
The measured Static Pressure is higher than
the acceptable mechanical limit of the
process connection elements.
Primary Variable Out of Range
Process value is outside its High or Low
working range
Device Diagnostic Mapping
This table shows the bit mapping of RB_x_ACTIVE and RB_EXTENDED_ACTIVE parameters with the relating error name and
NAMUR NE107 category.