76
2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
Cat. Error
RB_fail / maintenance / offspec / check_
ACTIVE (indexes 47, 48, 49, 50)
RB_EXTENDED_ACTIVE (index 69)
Electronic Interface error.
Exchange of non-critical data between sensor and
electronics is precluded due to problem in the
transmitter circuit of the electronics or in receiver
circuit of the sensor
Non-Volatile Sensor memory
burn error
Writings to the Sensor non-Volatile Memory were
not successful. The device works without problems
but any replacement operation is compromised
because the back-up configuration is not updated
Non-Volatile Electronics
memory burn error
Writings to the electronic Non-Volatile Memory
were not successful. The device continue to work
without problems but after the next power cycle
the last configuration will be lost
Replace Info
An element of the transmitter has been changed
(sensor or electronics) and the correct replacement
operation must be executed
The Replace operation is required after the
changing of the electronics or of the sensor.
Both the directions are allowed, from
Electronic (CB) to Sensor (FE) or from Sensor
(FE) to Electronic (CB)
The Replace operation is required after the
changing of the electronics or of the sensor
but it is allowed only from Electronic (CB) to
Sensor (FE)
The Replace operation has been attempted
but with wrong direction
PILD Output
The PILD algorithm has detected impulse lines
plugged. The Plugged Line can be one among:
PILD algorithm has detected both impulse
lines plugged.
PILD algorithm has detected a plugged
impulse line on the HIGH side.
PILD algorithm has detected a plugged
impulse line on the LOW side.
PILD algorithm has detected one plugged
impulse line.
PILD Changed Operating
Conditions
The pressure value currently detected is too
different from what used for the PILD Training
...Device Diagnostic Mapping