2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
77
Cat. Error Block err HMI code PRTB_x_VALUE Status
Electronics errors PRIMARY SECONDARY TERTIARY QUATERNARY PDP_TRIM SP_TRIM
Memory Failure RB.Lost NV Data BAD Device Failure No Limit
Electronic Interface
error.
RB.Device Needs
Maintenance Soon
GOOD_NC Non Specific No Limit
Non-Volatile memory
burn error
RB.Device Needs
Maintenance Soon
GOOD_NC Non Specific No Limit
Pressure sensor errors PRIMARY SECONDARY TERTIARY QUATERNARY PDP_TRIM SP_TRIM
Sensor Invalid
PRTB.Sensor
Failure
BAD Sensor Failure No Limit
Sensor Memory Fail
PRTB.Sensor
Failure
BAD Sensor Failure No Limit
P-dP Sensor Fail
PRTB.Sensor
Failure
BAD Sensor
Failure No Limit
GOOD_NC Non
Specific No
Limit
GOOD_NC
Non Specific
No Limit
BAD Sensor Failure No
Limit
GOOD_NC Non
Specific No
Limit
Static Pressure Sensor
Fail
PRTB.Sensor
Failure
UNCERTAIN
Sensor
Conversion Not
Accurate No
Limit
GOOD_NC Non
Specific No
Limit
BAD Sensor
Failure No
Limit
UNCERTAIN Sensor
Conversion Not Accurate
No Limit
BAD Sensor
Failure No Limit
Sensor Temperature
Fail
PRTB.Sensor
Failure
UNCERTAIN
Sensor
Conversion Not
Accurate No
Limit
BAD Sensor
Failure No
Limit
UNCERTAIN Sensor Conversion Not Accurate No Limit
NonVolatile memory
burn error
RB.Device Needs
Maintenance Soon
GOOD_NC Non Specific No Limit
Installation / start-up errors PRIMARY SECONDARY TERTIARY QUATERNARY PDP_TRIM SP_TRIM
Out of Service RB.Out of Service GOOD_NC Non Specific No Limit Note:The AI1,2,3 OUT Goes to BAD
Input Simulation
Active
PRTB.Local
Override
GOOD_NC Non Specific No Limit
Replace Info
RB.Device Needs
Maintenance Soon
GOOD_NC Non Specific No Limit
Process errors PRIMARY SECONDARY TERTIARY QUATERNARY PDP_TRIM SP_TRIM
Pressure Overrange PRTB.Other
BAD Non
Specific No
Limit
GOOD_NC Non Specific No
Limit
BAD Non Specific No Limit
GOOD_NC Non
Specific No
Limit
P-dP Out Of Limit PRTB.Other
UNCERTAIN
Non Specific No
Limit
GOOD_NC Non Specific No
Limit
UNCERTAIN Non Specific
No Limit
GOOD_NC Non
Specific No
Limit
Static Pressure Out Of
Limit
PRTB.Other
UNCERTAIN
Sensor
Conversion Not
Accurate No
Limit
GOOD_NC Non
Specific No
Limit
UNCERTAIN
Non Specific
No Limit
UNCERTAIN Sensor
Conversion Not Accurate
No Limit
UNCERTAIN
Non Specific
No Limit
Sensor Temperature
Out Of Limit
PRTB.Other
UNCERTAIN
Sensor
Conversion Not
Accurate No
Limit
UNCERTAIN
Non Specific
No Limit
UNCERTAIN Sensor Conversion Not Accurate No Limit
Max. Working Pressure
Exceeded
PRTB.Other GOOD_NC Non Specific No Limit
Diagnostic, BlOCK_ERR and Status Byte
In this table are grouped together the errors produced by the same item. In addition, for each error is specified the corresponding
standard BLOCK_ERR bit, the Error Code shown in the HMI Diagnostic page and the Status Byte assumed by the dynamic variables
of the Pressure Transducer Block.