2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
Configuration hints
The minimum configuration for having the AR working and/or moving out from the OOS needs at least the following settings:
Set ARITH_TYPE with a valid value. It must be different by 0 and in the range 1 – 9
If the selected ARITH_TYPE is in the range between 1-5 (limited functions), the output limits COMP_HI_LIM > COMP_LO_LIM
The BAL_TIME must be greater than the Block Execution Time
When the ARITH_TYPE = 6 (Average) in case of no inputs available the output will be set to NaN (Not a Number)
Set the GAIN with value different by 0
Block Mapping
Idx Parameter Description / Range / Selections / Note
BLOCK_OBJ
In the Block Object data structure, there are different items describing the block characteristics. Execution period,
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
ST_REV
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a static
parameter value (S – under Storage) in the block is changed.
TAG_DESC The user description of the intended application of the block
STRATEGY The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
ALERT_KEY The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
MODE_BLK
TARGET AUTO / MAN / OOS The selectable modes by the operator.
ACTUAL The mode the block is currently in.
PERMITTED AUTO / MAN / OOS Allowed modes that the target may take on
NORMAL AUTO The common mode for the Actual.
BLOCK_ERR
This parameter reflects the error status associated with the hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
PV The process variable used in block execution, expressed in PV_SCALE unit Code
OUT
The block output value calculated as a result of
the block execution, expressed in OUT_SCALE
unit
Writeable only if MODE_BLK.ACTUAL = MAN
PRE_OUT expressed in OUT_SCALE unit Displays what would be the OUT value and status if the mode was Auto or
lower.
 PV_SCALE The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be used in
displaying the PV parameter and parameters which have the same scaling as PV.
 OUT_RANGE The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be used in
displaying the scaling for the output. It has no effect on the block
 GRANT_DENY
 INPUT_OPTS
Options the user may select to alter the calculation done in a control loop
 IN Use uncertain as good
 IN_LO Use uncertain as good
 
 
 


 
 
 IN The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
 IN_LO Input for the low range transmitter, in a range extension application. Expressed in PV_SCALE Unit
  The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
  The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
  The Primary Input Value for the block coming from another block. Expressed in PV_SCALE Unit
 RANGE_HI Constant Value above which the range extension has switched to the high range transmitter Expressed in PV_SCALE Unit
 RANGE_LO Constant Value below which the range extension has switched to the low range transmitter Expressed in PV_SCALE Unit.