Idx Parameter Description / Range / Selections / Note
COMP_HI_LIM
The high limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
COMP_LO_LIM The low limit imposed on the PV compensation term. Expressed in PV_SCALE Unit Code
ARTH_TYPE
The identification number of the arithmetic algorithm
Flow Compensation, Linear
Flow Compensation, Square Root
Flow Compensation, Approximate
BTU Flow
Traditional Multiple Divide
Average
Traditional Summer
Fourth Order Polynomial
Simple HTG compensated Level
BAL_TIME
Expressed in OUT_SCALE Unit
The specified time for the internal working value of bias to return to operator set bias.
Also used to specify the time constant at which the integral term will move to obtain
balance when the output is limited and the mode is AUTO, CAS, or RCAS. Expressed in
seconds
BIAS Expressed in OUT_SCALE Unit
The bias value used in computing the function block output
GAIN
Dimensionless value used by the block algorithm in calculating the block output
OUT_HI_LIM
Expressed in OUT_SCALE Unit
Limits the maximum output value.
OUT_LO_LIM
Limits the minimum output value.
UPDATE_EV T This alert is generated by any change to the static data
BLOCK_ALM
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set the Active Status in the status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another block alert may be reported without clearing the Active Status, if the
subcode has changed