Optional I/O extension modules 161
Isolation areas:
Relay outputs (50…52, 53…55):
Wire size max. 1.5 mm
2
Minimum contact rating: 12 V / 10 mA
Maximum contact rating: 250 V AC / 30 V DC / 2 A
Maximum breaking capacity: 1500 VA
Transistor output (42…44):
Wire size max. 1.5 mm
2
Type: Transistor output PNP
Maximum switching voltage: 30 V DC
Maximum switching current: 100 mA / 30 V DC, short-circuit protected
Frequency: 10 Hz … 16 kHz
Resolution: 1 Hz
Inaccuracy: 0.2%
External power supply (40…41):
Wire size max. 1.5 mm
2
24 V AC / V DC ±10% (GND, user potential)
Maximum current consumption: 25 W, 1.04 A at 24 V DC
Symbol Description
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
DO1
CMOD-01
RO5
RO424 V
in
Plugged to
drive
SLOT2