EasyManua.ls Logo

ABB ACS580-07-0495A-4 - NPN Configuration for Digital Inputs (DIGITAL IN); Connection for Obtaining 0

ABB ACS580-07-0495A-4
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84 Control unit
NPN configuration for digital inputs (DIGITAL IN)
Internal and external +24 V power supply connections for NPN configuration are shown in
the figure below.
Connection for obtaining 0…10 V from analog output 2 (ANALOG IN/OUT)
To obtain 0…10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between analog output AO2 and analog common ground AGND.
Examples are shown in the figure below.
Internal +24 V power supply External +24 V power supply
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
NPN connection (sink)
NPN connection (sink)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
0VDC
+24 V DC
8 AO2 Analog output 2. Default output 0…20 mA.
9AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
500 ohm
8 AO2 Analog output 2. Default output 0…20 mA.
9AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
1kohm 1kohm
0…10 V
0…10 V

Table of Contents

Related product manuals