84 Control unit
NPN configuration for digital inputs (DIGITAL IN)
Internal and external +24 V power supply connections for NPN configuration are shown in
the figure below.
Connection for obtaining 0…10 V from analog output 2 (ANALOG IN/OUT)
To obtain 0…10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between analog output AO2 and analog common ground AGND.
Examples are shown in the figure below.
Internal +24 V power supply External +24 V power supply
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
NPN connection (sink)
NPN connection (sink)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
0VDC
+24 V DC
8 AO2 Analog output 2. Default output 0…20 mA.
9AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
500 ohm
8 AO2 Analog output 2. Default output 0…20 mA.
9AGND
Analog common ground. Internally connected to chassis
through a 2 Mohm resistor.
1kohm 1kohm
0…10 V