Electrical installation 77
Installing option modules
WARNING! Obey the instructions in chapter Safety instructions. If you ignore
them, injury or death, or damage to the equipment can occur.
1. Stop the drive and do the steps in section Precautions before electrical work on page
16 before you start the work.
Option slot 3 (embedded fieldbus adapter modules)
The drive is delivered with the standard embedded fieldbus adapter module CEIA-01
installed. If you have ordered another optional module, remove the CEIA-01 module by
carefully bending the retaining clips to the sides while pulling the module outward, and put
the other module carefully into its position.
Option slot 2 (I/O extension modules)
1. Put the module carefully into its position on the control unit.
2. Tighten the mounting screw.
3. Tighten the grounding screw (CHASSIS) to 0.8 m. Note: The screw grounds the
module. It is necessary for fulfilling the EMC requirements and for correct operation of
the module.
Option slot 1 (fieldbus adapter modules)
1. Put the module carefully into its position on the control unit.
2. Tighten the mounting screw (CHASSIS) to 0.8 N·m. Note: The screw tightens the
connections and grounds the module. It is necessary for fulfilling the EMC
requirements and for correct operation of the module.
Wiring the optional modules
See the appropriate optional module manual for specific installation and wiring
instructions.

Table of Contents