Electrical installation 65
6
Electrical installation
Contents of this chapter
This chapter gives instructions on the wiring the drive.
Warnings
WARNING! If you are not a qualified electrician do not do the installation work
described in this chapter. Obey the instructions in chapter Safety instructions. If
you ignore them, injury or death, or damage to the equipment can occur.
Checking the insulation of the assembly
Drive
Do not make any voltage tolerance or insulation resistance tests on any part of the drive as
testing can damage the drive. Every drive has been tested for insulation between the main
circuit and the chassis at the factory. Also, there are voltage-limiting circuits inside the
drive which cut down the testing voltage automatically.
Input cable
Check the insulation of the input cable according to local regulations before connecting it
to the drive.