59
SPECIFICATION
Relay outputs
Number of relays
Three supplied as standard,
configurable to one or both sensor inputs or status
Set point adjustment
Fully programmable as normal or failsafe, high/low or status
Hysteresis
Programmable 0 to 5% in 0.1% increments
Delay
Programmable 0 to 100 minutes in 1 minute intervals
Relay contacts
Single-pole changeover
Rating 5A 115/230V AC, 5A DC
Insulation
2kV RMS contacts to earth/ground
Power supply
Voltage requirements
85 to 260V AC 50/60 Hz
Optional 9 to 36V DC
Power consumption
<24VA
Insulation
Mains to earth (line to ground) 2kV RMS
Mechanical Data
Transmitter
IP66/NEMA4X
Dimensions 192mm (7.56 in.) high x 230mm (9.06 in.) wide x
94mm (3.7 in.) deep
Weight 1kg (2.2 lb)
Sensor
Low Range Dimensions 327mm (12.87 in.) wide
x 410mm (16.14 in.) high x 162mm (6.38 in) deep
High Range Dimensions 405mm (15.94 in.) wide
x 373mm (14.68 in.) high x 136mm (5.35 in) deep
Weight 6kg (13.2 lb)
Environmental Data
Operating temperature limits
0 to 50°C (32 to 122°F)
Storage temperature limits
–25 to 75°C (–13 to 167°F)
Operating humidity limits
Up to 95%RH non-condensing
EMC emissions and immunity
Meets requirements of:
EN61326 (for an industrial environment)
EN50081-2
EN50082-2
Safety
EN61010-1
Overvoltage Class II on inputs and outputs
Pollution Category 2
Cable entry types
Standard 5 or 7 x M20 cable glands
N. American 7 x knockouts suitable for
1
/
2
in. Hubble gland
SS/AV4ORG Issue 3