AWT420 | UNIVERSAL 4-WIRE, DUAL-INPUT TRANSMITTER | OI/AWT420-EN REV. B
15
Standard sensors without diagnostic functions
NOTICE
Ensure sensor diagnostics are Off when using standard
sensors without diagnostic functions.
Sensor type RTD wiring
SENSE
1
GUARD
2
REF
3
S.GND
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Clear Black Red White
Blue Black Red White
Clear Black
Red
Red
White
Clear Black White Red Red
Blue Black Red White
Blue Black Red White Grey
Blue Black Red White Yellow
Blue Black Red White Yellow Grey
Standard sensors with diagnostic functions
NOTICE
Ensure sensor diagnostics are On when using standard
sensors with diagnostic functions.
Sensor type RTD wiring
SENSE
1
GUARD
2
REF
3
S.GND
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Blue Yellow Black Green Red White
Clear Red Blue Green/Yellow Red White
Clear Red Blue Green/Yellow Red White Grey
Conductivity sensor module connections
2-electrode sensors
Sensor type RTD wiring
DRIVE +
1
2
3
DRIVE –
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Red Black Green/Yellow Blue Brown
Red Black Brown Green/Yellow Blue
Red Blue Yellow
Green Black Blue Yellow
Green Black Blue/Red Yellow
Green Black Yellow Red Blue
attached cells
4-electrode sensors
Sensor type RTD wiring
DRIVE +
1
SENSE +
2
SENSE –
3
DRIVE –
4
RTD 1
5
RTD 2
6
SHIELD
7
RTD 3
8
Green Red White Black Blue Yellow