Configuring DNP OPC Server properties3.4.2.
Table 3.4.2-1 DNP OPC Server properties
DescriptionValue or Value range/DefaultProperty/Parameter
Basic
Instance identification of dia-
gnostic OPC alarm and event
server.
Prog ID AE
Instance identification of dia-
gnostic OPC data access
server.
Prog ID DA
Configuring DNP OPC Server LAN Channel properties3.4.3.
The DNP OPC Server LAN Channel properties that can be configured and value ranges
for them can be found in Table 3.4.3-1. The actual configuration by using Communication
Engineering Tool (CET) is performed as described in 3.4.1, General about configuring
objects.
Table 3.4.3-1 DNP LAN Channel properties
DescriptionValue or Value range/DefaultProperty/Parameter
Basic
Specifies if channel is in use or
not.
In Use
Not In Use
Default: In Use
In use
Communication Port
IP address of Ethernet interface
in COM610.
127.0.0.1Local Address
Communication Control
Specifies if incoming connec-
tion requests are checked.
True
False
Default: True
Check Connection Request
Maximum time in milliseconds
of the TCP connect operation.
0 to 65535
Default: 500
Connection timeout
Connectin protocol used.TCP/IP
UDP/IP
Default: TCP/IP
Connection Type
23
DNP 3.0
LAN/WAN Master
(OPC) 3.2
COM600 Station Automation Series
1MRS756566
User's Guide