DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Object number for indication.Binaryinput(1,2)
Binaryoutput(10)
Default: Binaryinput(1,2)
Indication Object
Controllable integer status (INC)3.4.8.12.
Table 3.4.8.12-1 Configurable INC properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850
INCCommon Data
Class
Addresses
Control index.-1 to 65535
Default: -1
Control Index
Index.-1 to 65535
Default: -1
Index
Data Class Spe-
cific
Object number for control.Default: Analog control output
block (41).
Control Object
Variation for control.0 to 65535
Default: 2
Control Variation
Object number for indication.Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Indication Object
Scale and Unit
Scale to be used with this type.Default: NoneScale