Controllable single point (SPC)3.4.8.17.
Table 3.4.8.17-1 Configurable SPC properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
SPCCommon Data
Class
Addresses
Control index.-1 to 65535
Default: -1
Control Index
Indication index.-1 to 65535
Default: -1
Indication Index
Data Class Spe-
cific
Momentary
Pulse
Latch
Default: Momentary
Control Code Quali-
fier
Object number for control.Default: Binary control output
block (12).
Control Object
Variation for control.0 to 65535
Default: 1
Control Variation
Object number for indication.Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Indication Object
Specifies using two-step, select-before-
operate method for issuing control request
or not.
Direct Operate
Select Before Operate
Default: Direct Operate
Operate
Single point status (SPS)3.4.8.18.
Table 3.4.8.18-1 Configurable SPS properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
42
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide