ABB COM600 Station Automation Series - Controllable Double Point (DPC); Controllable Integer Status (INC); Binary Controlled Step Position Information (BSC)

ABB COM600 Station Automation Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Controllable double point (DPC)5.2.15.
OPC data typesDNP data object
field
Mandat-
ory/Optional
Value/Value rangeTypeName
VT_BOOLState (0:OFF,
1:ON)
MFALSE | TRUEBOOLEANstVal
VT_BOOLControl CodeOFALSE | TRUEBOOLEANctlOperOn
VT_BOOLControl CodeOFALSE | TRUEBOOLEANctlOperOff
VT_BOOLControl CodeOFALSE | TRUEBOOLEANctlSelOn
VT_BOOLControl CodeOFALSE | TRUEBOOLEANctlSelOff
VT_BOOL-OFALSE | TRUEBOOLEANctlCan
VT_BOOLControl CodeOFALSE | TRUEBOOLEANstSelt
VT_I4DNP statusMQualityq
VT_DATE<server provided if
none> | Time of
occurrence | MSEC
MTimeStampt
VT_BSTR-OTextDescriptiond
Controllable integer status (INC)5.2.16.
OPC data typesDNP data object
field
Mandat-
ory/Optional
Value/Value rangeTypeName
VT_I4Control CodeM-INTEGERctlVal
VT_I4Current ValueMFALSE | TRUEBOOLEANstVal
VT_I4DNP statusMQualityq
VT_DATE<server provided if
none> | Time of
occurrence | MSEC
MTimeStampt
VT_BSTR-OTextDescriptiond
Binary controlled step position information (BSC)5.2.17.
OPC data typesDNP data object
field
Mandat-
ory/Optional
Value/Value rangeTypeName
VT_I1Control CodeMstop (0) | lower (1)
| higher (2) |
reserved (3)
ENUMERATEDctlVal
VT_I4StateMValWithTransvalWTr
62
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide

Table of Contents