EasyManua.ls Logo

ABB COM600 Station Automation Series - Configuring Data Objects

ABB COM600 Station Automation Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring data objects3.4.8.
General about configuring data objects3.4.8.1.
Object properties of the data objects are listed in the following tables.
When configuring address values for DNP IED data objects, the valid address range is
0 to 65535. If the value is -1, then the address is not available.
Directional protection activation information (ACD)3.4.8.2.
Table 3.4.8.2-1 Configurable ACD properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
ACDCommon Data
Class
Addresses
General Index-1 to 65535
Default: -1
General Index
Neutral Index-1 to 65535
Default: -1
Neutral Index
Phase A Index-1 to 65535
Default: -1
Phase A Index
Phase B Index-1 to 65535
Default: -1
Phase B Index
Phase C Index-1 to 65535
Default: -1
Phase C Index
Data Class Spe-
cific
Object number for indication.Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Indication Object
30
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide

Table of Contents

Related product manuals