Configuring data objects3.4.8.
General about configuring data objects3.4.8.1.
Object properties of the data objects are listed in the following tables.
When configuring address values for DNP IED data objects, the valid address range is
0 to 65535. If the value is -1, then the address is not available.
Directional protection activation information (ACD)3.4.8.2.
Table 3.4.8.2-1 Configurable ACD properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
ACDCommon Data
Class
Addresses
General Index-1 to 65535
Default: -1
General Index
Neutral Index-1 to 65535
Default: -1
Neutral Index
Phase A Index-1 to 65535
Default: -1
Phase A Index
Phase B Index-1 to 65535
Default: -1
Phase B Index
Phase C Index-1 to 65535
Default: -1
Phase C Index
Data Class Spe-
cific
Object number for indication.Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Indication Object
30
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB COM600 Station Automation Series and is the answer not in the manual?

ABB COM600 Station Automation Series Specifications

General IconGeneral
BrandABB
ModelCOM600 Station Automation Series
CategoryController
LanguageEnglish

Related product manuals