DescriptionValue or Value range/ DefaultName
Controls whether the device communica-
tion is initially in use or not.
In use
Not in use
Default: In use
In Use
Specifies whether the device is in simula-
tion mode or not.
True
False
Default: False
Simulation Mode
If True, then no events will be generated
for IED if the new value and quality are the
same as the current value and quality.
True
False
Event only with
changed value
If True, no is event generated when the
item tag is updated for the first time.
True
False
Suppress event on
first update
Addresses
Defines the internet address of this IED.127.0.0.1Internet Address
Station address of the master station.0 to 65535
Default: 1
Master Address
Station address of the DNP 3.0 slave sta-
tion.
0 to 65535
Default: 1
Slave Address
Communication
Control
Allocating application of the station.0 to 32
Default: 0
Allocating Applica-
tion
When true, consequent application layer
response timeouts set the station to sus-
pended state and the corresponding pro-
cess objects are set to invalid state.
True
False
Default: False
Automatic Suspen-
sion
Address offset between the process
objects for static data and events with the
same DNP 3.0 address (index).
0 to 65535
Default: 0
Event Offset
Then length of pulse in milliseconds used
in the output commands of the control
relay.
0 to 65535
Default: 0
Pulse Length Off
For Control Relay
Output
Then length of pulse in milliseconds used
in the output commands of the control
relay.
0 to 65535
Default: 0
Pulse Length On
For Control Relay
Output
When True, a static data (class 0) poll
request is always sent when the object
status of the DNP master station gets the
value zero (0).
True
False
Default: True
Static Datapoll
25
DNP 3.0
LAN/WAN Master
(OPC) 3.2
COM600 Station Automation Series
1MRS756566
User's Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB COM600 Station Automation Series and is the answer not in the manual?

ABB COM600 Station Automation Series Specifications

General IconGeneral
BrandABB
ModelCOM600 Station Automation Series
CategoryController
LanguageEnglish

Related product manuals