Chapter 4 TwelvePulse Serial / Sequential Configurations with DCS 600
II F2
4 - 8 DCS 600 Manual for 12 Pulse Operation
Measuring the DC voltage
(serial / sequential mode)
[continued]
Solution 1
:
SDCS-PIN-51
high-resistance
measurement
For Solution 1 the hardware coding of the voltage measurement
channels of the standard converters must be rescaled.
Note: This SDCS-PIN-51 modification (Solution 1) is possible up
to a rated supply voltage 500 V AC!
Complete 12 pulse serial and sequential configurations
including units of the series DCA 600 enclosed con-
verters as delivered from ABB already feature the
required rescaling measures as an option.
Rated line (supply)
voltage [V]
SDCS-PIN-51
voltage coding *)
Software coding
S CON NOM VOLT
(42.08)
200 250 **) 500 500
250 300 600 600
300 350 690 690
350 400 790 800
400 500 1000 1000
*) See Manual Technical Data (resistors W1 W 26)
**) No changes of voltage coding are required for 400 V and 500 V
standard converters of size C4!