18 DPA 250 S4 50-250 KW OPERATING MANUAL
—
3.3 System configuration
3.3.1 Standalone configuration
3.3.2 Parallel system configuration
below, standard configurations are listed and described.
Number of modules
1 x 50 kW 2 x 50 kW 3 x 50 kW 4 x 50 kW 5 x 50 kW 6 x 50 kW
Maximum load
50 kW 100 kW 150 kW 200 kW 250 kW 250 kW
Configuration with maximum load
Note: Depending on the actual load level system features automatically redundancy.
The DPA 250 S4 UPS unit can be paralleled to increase the power capacity up to 1500kW. Up to 6 UPS
units with 30 UPS modules can be configured as shown in the table below:
Number of UPS units
1 x 250 kW 2 x 250 kW 3 x 250 kW 4 x 250 kW 5 x 250 kW 6 x 250 kW
Maximum load
250 kW 500 kW 750 kW 1000 kW 1250 kW 1500 kW
Maximum number of UPS Modules
6 12 18 23 29 30
Configuration with maximum load per frame
Note: Depending on the actual load level system features automatically redundancy.