9 INSTALL ATION
9.2 UPS location
The minimum needed clearances to allow for the correct airflow on the UPS system and to allow proper
service and maintenance shall be respected as indicated below:
SINGLE DPA 250 S4 FRAME
UPS PARALLEL SYSTEM SIDE
BY SIDE INSTALLATION OR
BATTERY CABINETS IN ROW.
A Back clearance for ventilation
(forced air outlet)
200 mm 300 mm
B Front clearance needed to allow
a correct door opening
1000 mm
C Maximum door opening angle 
D Top Clearance
(Top clearance is only needed if
there is no side clearance)
400 mm
9.2-1: DPA 250 S4
clearances
9.2-1