Block Terminal Contact Signal On Display Function
- Common
-
Relays AUX
(Function on request, to be defined)
-
COMMON_ALARM Common
ALARM No Alarm Condition
Common Alarm (System)
LOAD_ON_MAINS Common
Message No Load on Bypass
Load On Bypass (Mains)
BATT_LOW Common
ALARM Battery Ok
Battery Low
LOAD_ON_INV Common
Message No Load on Inverter
Load on Inverter
MAINS_OK Common
ALARM Mains Failure
Mains Present
-
EXT_MAN_BYP
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT
-
5.3.2 Output dry port (X2 and X1)
X2 terminals can hold Cable from 0.2mm2 – 1.5mm2
X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A