Block Terminal Contact Signal On Display Function


C
NC
NO
- Common
 -
Relays AUX
(Function on request, to be defined)
 -

C
NC
NO
COMMON_ALARM Common
 ALARM No Alarm Condition
 Common Alarm (System)

C
NC
NO
LOAD_ON_MAINS Common
 Message No Load on Bypass
 Load On Bypass (Mains)

C
NC
NO
BATT_LOW Common
 ALARM Battery Ok
 Battery Low

C
NC
NO
LOAD_ON_INV Common
 Message No Load on Inverter
 Load on Inverter

C
NC
NO
MAINS_OK Common
 ALARM Mains Failure
 Mains Present


-
EXT_MAN_BYP
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT
 -
5.3.2 Output dry port (X2 and X1)
X2 terminals can hold Cable from 0.2mm2 – 1.5mm2
X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A