26 DPA 250 S4 50-250 KW OPERATING MANUAL
3.4.6 UPS measure, control & monitoring element description
3.4.6-1
3.4.6-1: UPS measure,
control & monitor-
ing elements
Ref DES Component Functional description
A40 Parallel board
Provides communication between the UPS modules
to monitor operating status and load sharing.
Provides a Sync port to synchronize the UPS output
with an external sources.
For details refer to chapter "5 Control & Monitoring"
A60 Interface board
Acquires the status of the output and maintenance
bypass switches
Acquires the battery temperature value
Provides 5 digital inputs and 5 output relays
Provides RS232 interface and USB port to monitor
the UPS by using the Wavemon software
For details refer to chapter "5 Control & Monitoring"
A65
UPS Network management
card (NMC) (optional)
The UPS network management card provides remote
monitoring via web by using SNMP, Modbus RS-485
and Modbus TCP/IP
For details refer to chapter "5 Control & Monitoring"
A61 DPA 250 S4 HMI (optional)
The touchscreen graphical display allows the operator
to control and monitor the UPS system.
For details refer to chapter "5 Control & Monitoring"