40 DPA 250 S4 50-250 KW OPERATING MANUAL
The control and navigation buttons allow the user to perform settings and adjustments, monitor the
voltages, currents, frequencies, power measurements and scroll the main and sub-menus in the UPS
module.
BUTTON FUNCTION
By pressing UP button
Scroll up the sub-menu or setting/parameter
When performing a setting/adjustment increase the value or parameter
By pressing DOWN button
Scroll down the sub-menu or setting/parameter
When performing a setting/adjustment decrease the value or parameter
By pressing BACK button
Scroll back to top level menu.
Cancel any setting/parameter and back to the previous value
Cancel the audible alarm emitted by the buzzer
By pressing ENTER button
Enter into the selected sub-menu
When performing a setting/parameter confirm and enter the value
After the start-up of the UPS module, by pressing any button, the Main menu is displayed.
5.2.1.3 Control and navigation buttons
The user is able to identify the status of the bypass, rectifier, battery and UPS output and the alarm by
reading the LED indicators. The LEDs are always active even if the display is in screensaver mode.
BYPASS LED (L2)
Green: bypass mains is available
Red: bypass main is not available or out of voltage/frequency toler-
ance
RECTIFIER LED (L1)
Green: rectifier mains is available
Red: rectifier mains is not available or out of voltage/frequency toler-
ance
BATTERY LED
Green: the battery is connected and charged
Flashing green: battery mode or battery test is performed
Red : battery failure, battery voltage/temperature high or performed
battery test is not ok
Flashing red : battery is not detected or disconnected
Yellow : battery low/discharged
OUTPUT LED
Green : UPS module output is available and supplied by the inverter
Yellow: UPS module output is available and supplied by the STATIC
bypass
Blue: UPS module is in Standby Mode (XTRA-VFI)
Non lighted: Load OFF or Q2 open
ALARM LED
Non lighted: no events/alarms pending
Yellow: events pending
Red: common alarm
5.2.1.4 LED status indicators